Appendix C to 29 CFR 1910.269 (section III.A, definitions) describes a ground mat, also called a grounding grid, as a metallic mat or grating, installed temporarily or permanently, that establishes an equipotential surface and provides points for attaching grounds. The buried grid of a switchyard or substation is the permanent form; the appendix explains that an equipotential zone protects the workers within it and not those wholly or partly outside it.
Appendix C to 29 CFR 1910.269 (section II.B) describes step potential as the voltage between the feet of a person standing near an energized grounded object, the electrode, while fault current flows through the earth; the voltage gradient at the surface puts a difference in potential across the person's stance, so a person near the object during a fault can be injured without touching anything. The industry term for the same quantity is step voltage.
Under 29 CFR 1910.269, conductive fences around substations are grounded, and when a substation fence is expanded or a section is removed the fence sections are isolated, grounded or bonded as necessary to protect employees from hazardous differences in electric potential; the regulation's note points to IEEE 80 for guidance on protection against such differences. The requirement is paragraph (u)(3).
Appendix C to 29 CFR 1910.269 (section II.B) describes touch potential as the voltage between an energized grounded object, the electrode, and the feet of a person in contact with the object while fault current flows; a voltage carried by a bonded structure, vehicle or ground lead to a point away from the electrode is called a transferred touch potential in the same sense. The industry term for the quantity is touch voltage.