- Appendix C to 29 CFR 1910.269 (section III.A, definitions) describes a ground mat, also called a grounding grid, as a metallic mat or grating, installed temporarily or permanently, that establishes an equipotential surface and provides points for attaching grounds. The buried grid of a switchyard or substation is the permanent form; the appendix explains that an equipotential zone protects the workers within it and not those wholly or partly outside it.
Elsewhere in the family
- Temporary protective grounding related entry on Arc Flash Reference
Sources
- 29 CFR 1910.269, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), current edition, OSHA. Cited: clause Appendix C, III.A. Regulation text. Held as: Government work. Agency copy of 29 CFR 1910.269
Also stated in
- Source passage: 29 CFR 1910.269, Appendix C, section III.A, definition of "ground mat (grounding grid)" (eCFR current as of 2026-10-26).
Read the reference passage
III. Protecting Workers From Hazardous Differences in Electrical Potential - A. Definitions
"Ground mat (grounding grid). A temporarily or permanently installed metallic mat or grating that establishes an equipotential surface and provides connection points for attaching grounds."
29 CFR 1910.269, Appendix C, section III.A, definition of "ground mat (grounding grid)", eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- Stated independently by FIST 5-1, section 8 Background, page 31 (July 2005).
Read the reference passage
8. Switchyard and Substation Protective Grounding
"Both threephase and single-phase-to-ground faults should be considered when determining the maximum available fault current at a grounded worksite. Buried ground mat conductors should be present within the confines (perimeter fence) of the station. The ground mat provides a common and permanent grounding electrode for bonding all non-current carrying conductive parts of equipment in the station (circuit breaker and transformer tanks, metal structures, fencing, etc.). It also conducts ground fault current into the earth which returns to remote grounded current sources."
FIST 5-1, section 8 Background, page 31, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 8 Background, page 32 (July 2005).
Read the reference passage
8. Switchyard and Substation Protective Grounding
"Within the perimeter fence of the station, the ground mat should control all step and touch potentials to safe levels during a ground fault. An exception to this rule may be in areas of the yard without equipment (empty bays) and lacking buried ground mat conductors. The ground mat also provides the ground electrode connection for protective grounds."
FIST 5-1, section 8 Background, page 32, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
Changelog (1 entry)
| Date | Revision | Change |
|---|---|---|
| 2026-11-02 | created (gloss.ground-mat.osha1910-269.definition) |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Ground mat." Grounding Reference. 2026-11-02. https://www.groundingreference.com/glossary/ground-mat/.
Grounding Reference, Ground mat (Nov. 2, 2026), https://www.groundingreference.com/glossary/ground-mat/.
@misc{etr-glossary-ground-mat,
title = {Ground mat},
howpublished = {\url{https://www.groundingreference.com/glossary/ground-mat/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-11-02}
}{{cite web |title=Ground mat |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/glossary/ground-mat/ |date=2026-11-02 |access-date=}}