Glossary

Defined terms used across electrical testing, each with its definition and the source that defines it.

  1. Ground mat

    Appendix C to 29 CFR 1910.269 (section III.A, definitions) describes a ground mat, also called a grounding grid, as a metallic mat or grating, installed temporarily or permanently, that establishes an equipotential surface and provides points for attaching grounds. The buried grid of a switchyard or substation is the permanent form; the appendix explains that an equipotential zone protects the workers within it and not those wholly or partly outside it.

  2. Step voltage

    Appendix C to 29 CFR 1910.269 (section II.B) describes step potential as the voltage between the feet of a person standing near an energized grounded object, the electrode, while fault current flows through the earth; the voltage gradient at the surface puts a difference in potential across the person's stance, so a person near the object during a fault can be injured without touching anything. The industry term for the same quantity is step voltage.

  3. Substation fence grounding

    Under 29 CFR 1910.269, conductive fences around substations are grounded, and when a substation fence is expanded or a section is removed the fence sections are isolated, grounded or bonded as necessary to protect employees from hazardous differences in electric potential; the regulation's note points to IEEE 80 for guidance on protection against such differences. The requirement is paragraph (u)(3).

  4. Touch voltage

    Appendix C to 29 CFR 1910.269 (section II.B) describes touch potential as the voltage between an energized grounded object, the electrode, and the feet of a person in contact with the object while fault current flows; a voltage carried by a bonded structure, vehicle or ground lead to a point away from the electrode is called a transferred touch potential in the same sense. The industry term for the quantity is touch voltage.