Substation fence grounding

Updated 2026-11-02

Data records

  • Under 29 CFR 1910.269, conductive fences around substations are grounded, and when a substation fence is expanded or a section is removed the fence sections are isolated, grounded or bonded as necessary to protect employees from hazardous differences in electric potential; the regulation's note points to IEEE 80 for guidance on protection against such differences. The requirement is paragraph (u)(3). Source: 29 CFR 1910.269, current edition, clause (u)(3). Verified 2026-11-02. Record gloss.substation-fence-grounding.osha1910-269.requirement

Sources

  • 29 CFR 1910.269, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), current edition, OSHA. Cited: clause (u)(3). Regulation text. Held as: Government work. Agency copy of 29 CFR 1910.269

Also stated in

  • Stated independently by NAVFAC MO-201, section 3.8.1.3, PDF page 109, printed 3-57, items (e) to (g) (April 1990).
    Read the reference passage

    3.8.1.3 Grid Design

    "(e) Oil circuit breakers require two grounds. (f) Station fences require complete perimeter ground cables, located three feet outside the fences, and are connected to the station grid. Ground spacing should not exceed 75 feet. Fences require a fabric ground for approximately every 75 feet and a post ground for every third post. (g) All station gates require connection to both gate posts and copper braid to connect the hinge posts to the gate."

    NAVFAC MO-201, section 3.8.1.3, PDF page 109, printed 3-57, items (e) to (g), April 1990. Agency copy of NAVFAC MO-201

    The current standard governs; this passage is a public-domain description of the practice dated April 1990.

Changelog (1 entry)
DateRevisionChange
2026-11-02created (gloss.substation-fence-grounding.osha1910-269.requirement)

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Substation fence grounding." Grounding Reference. 2026-11-02. https://www.groundingreference.com/glossary/substation-fence-grounding/.
Grounding Reference, Substation fence grounding (Nov. 2, 2026), https://www.groundingreference.com/glossary/substation-fence-grounding/.
@misc{etr-glossary-substation-fence-grounding,
  title = {Substation fence grounding},
  howpublished = {\url{https://www.groundingreference.com/glossary/substation-fence-grounding/}},
  organization = {Grounding Reference},
  publisher = {Grounding Reference},
  year = {2026},
  note = {last substantive change 2026-11-02}
}
{{cite web |title=Substation fence grounding |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/glossary/substation-fence-grounding/ |date=2026-11-02 |access-date=}}