Data record gloss.substation-fence-grounding.osha1910-269.requirement

Verified 2026-11-02 Confidence: High

Under 29 CFR 1910.269, conductive fences around substations are grounded, and when a substation fence is expanded or a section is removed the fence sections are isolated, grounded or bonded as necessary to protect employees from hazardous differences in electric potential; the regulation's note points to IEEE 80 for guidance on protection against such differences. The requirement is paragraph (u)(3).

Provenance29 CFR 1910.269 supports data record gloss.substation-fence-grounding.osha1910-269.requirement, which is cited on the entry Substation fence grounding.SOURCE29 CFR 1910.26929 CFR 1910.269Regulation, clause (u)(3)DATA RECORDgloss.substation-fence-grounding.osha1910-269.requirementgloss.substation-fence-g..Verified 2026-11-02ENTRYSubstation fence groundingSubstation fence groundingNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
Source29 CFR 1910.269Regulation, clause (u)(3)
Data recordgloss.substation-fence-grounding.osha1910-269.requirementVerified 2026-11-02
EntrySubstation fence groundingNo revisions
Subject
Substation fence grounding (Glossary)
Kind
Standard scope
Source
29 CFR 1910.269, current edition, clause (u)(3), 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
Also stated in
  • Stated independently by NAVFAC MO-201, section 3.8.1.3, PDF page 109, printed 3-57, items (e) to (g) (April 1990).
    Read the reference passage

    3.8.1.3 Grid Design

    "(e) Oil circuit breakers require two grounds. (f) Station fences require complete perimeter ground cables, located three feet outside the fences, and are connected to the station grid. Ground spacing should not exceed 75 feet. Fences require a fabric ground for approximately every 75 feet and a post ground for every third post. (g) All station gates require connection to both gate posts and copper braid to connect the hinge posts to the gate."

    NAVFAC MO-201, section 3.8.1.3, PDF page 109, printed 3-57, items (e) to (g), April 1990. Agency copy of NAVFAC MO-201

    The current standard governs; this passage is a public-domain description of the practice dated April 1990.

Beside
gloss.ground-mat.osha1910-269.definition; gloss.touch-voltage.osha1910-269.definition; gloss.step-voltage.osha1910-269.definition

History

Every recorded change to this data record, oldest first.
DateChange
2026-11-02created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.substation-fence-grounding.osha1910-269.requirement." Grounding Reference. 2026-11-02. https://www.groundingreference.com/data/gloss.substation-fence-grounding.osha1910-269.requirement/.
Grounding Reference, Data record gloss.substation-fence-grounding.osha1910-269.requirement (Nov. 2, 2026), https://www.groundingreference.com/data/gloss.substation-fence-grounding.osha1910-269.requirement/.
@misc{etr-data-gloss-substation-fence-grounding-osha1910-269-requirement,
  title = {Data record gloss.substation-fence-grounding.osha1910-269.requirement},
  howpublished = {\url{https://www.groundingreference.com/data/gloss.substation-fence-grounding.osha1910-269.requirement/}},
  organization = {Grounding Reference},
  publisher = {Grounding Reference},
  year = {2026},
  note = {last substantive change 2026-11-02}
}
{{cite web |title=Data record gloss.substation-fence-grounding.osha1910-269.requirement |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/gloss.substation-fence-grounding.osha1910-269.requirement/ |date=2026-11-02 |access-date=}}