Data record gloss.step-voltage.osha1910-269.definition
Verified 2026-10-29 Confidence: High
Appendix C to 29 CFR 1910.269 (section II.B) describes step potential as the voltage between the feet of a person standing near an energized grounded object, the electrode, while fault current flows through the earth; the voltage gradient at the surface puts a difference in potential across the person's stance, so a person near the object during a fault can be injured without touching anything. The industry term for the same quantity is step voltage.
| Step | Item | Detail |
|---|---|---|
| Source | 29 CFR 1910.269 | Regulation, clause Appendix C, II.B |
| Data record | gloss.step-voltage.osha1910-269.definition | Verified 2026-10-29 |
| Entry | Step voltage | No revisions |
- Subject
- Step voltage (Glossary)
- Kind
- Definition
- Source
- 29 CFR 1910.269, current edition, clause Appendix C, II.B, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
- Also stated in
- Source passage: 29 CFR 1910.269, Appendix C, section II.B (the ellipsis drops a sentence that refers to Figure 1) (eCFR current as of 2026-10-26).
Read the reference passage
II. Voltage-Gradient Distribution - B. Step and touch potentials
"Step potential is the voltage between the feet of a person standing near an energized grounded object (the electrode). [...] A person could be at risk of injury during a fault simply by standing near the object."
29 CFR 1910.269, Appendix C, section II.B (the ellipsis drops a sentence that refers to Figure 1), eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- Stated independently by FIST 5-1, section 8 Background, page 32 (July 2005).
Read the reference passage
8. Switchyard and Substation Protective Grounding
"Within the perimeter fence of the station, the ground mat should control all step and touch potentials to safe levels during a ground fault. An exception to this rule may be in areas of the yard without equipment (empty bays) and lacking buried ground mat conductors. The ground mat also provides the ground electrode connection for protective grounds."
FIST 5-1, section 8 Background, page 32, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, Appendix F1 A, page 65 (July 2005).
Read the reference passage
A. Connection to True Earth
"The closer a person is to the ground rod or the tower leg or the down guy, the greater the concentration of the current and the higher the voltage. The wider apart a person's legs are, or the greater the distance from the legs on the ground to the hands on the steel, the larger the voltage difference across the body. For this reason groundmen are cautioned to stay clear of structures at the ground surface level."
FIST 5-1, Appendix F1 A, page 65, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, Appendix F1 B, page 65 (July 2005).
Read the reference passage
B. Step Potential
"Step potential is caused by fault current through the earth. The current creates a voltage drop at the earth's surface. A person standing with feet apart bridges a portion of this drop. This places a potential difference from foot to foot."
FIST 5-1, Appendix F1 B, page 65, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 15-13.c, PDF page 168, printed 15-4, item (3); items (1) and (2) are a fragment and an ASTM F 855 reference (29 November 1996).
Read the reference passage
15-13.c. Safety aspects
"Staying at least 10 feet (3 meters) clear of any protective grounds is recommended to avoid touch-and-step potentials. Otherwise, wear insulated footwear and provide other hazard minimizing measures."
TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082, section 15-13.c, PDF page 168, printed 15-4, item (3); items (1) and (2) are a fragment and an ASTM F 855 reference, 29 November 1996. Agency copy of TM 5-684 / NAVFAC MO-200 / AFJMAN 32-1082
The current standard governs; this passage is a public-domain description of the practice dated 29 November 1996.
- Stated independently by UFM 3-560-01, section 7-8, page 83; the ellipsis drops the sentence pointing to Table 7-9, and the paragraph's last sentence on bonding separately grounded systems is left out for the word limit (13 March 2026).
Read the reference passage
7-8 PLACEMENT OF GROUNDS
"Install grounds as close as possible to the work. [...] Never approach closer than distances specified in Table 3-1 until after the line/equipment has been isolated, deenergized, tested, and properly grounded. Afterwards, avoid coming closer than 10 ft (3.0 m) to minimize the hazard from step and touch potentials. Such potential differences occur from items such as down guys, ground rods, maintenance vehicles, and structure legs or ground wires during the period in which they are bonded to temporary grounds. When it is absolutely necessary to work on or near these features, use bonded conductive or insulated platforms, or approved insulated footwear to minimize the hazard from step and touch potentials."
UFM 3-560-01, section 7-8, page 83; the ellipsis drops the sentence pointing to Table 7-9, and the paragraph's last sentence on bonding separately grounded systems is left out for the word limit, 13 March 2026. Agency copy of UFM 3-560-01
The current standard governs; this passage is a public-domain description of the practice dated 13 March 2026.
- Source passage: 29 CFR 1910.269, Appendix C, section II.B (the ellipsis drops a sentence that refers to Figure 1) (eCFR current as of 2026-10-26).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record gloss.step-voltage.osha1910-269.definition." Grounding Reference. 2026-10-29. https://www.groundingreference.com/data/gloss.step-voltage.osha1910-269.definition/.
Grounding Reference, Data record gloss.step-voltage.osha1910-269.definition (Oct. 29, 2026), https://www.groundingreference.com/data/gloss.step-voltage.osha1910-269.definition/.
@misc{etr-data-gloss-step-voltage-osha1910-269-definition,
title = {Data record gloss.step-voltage.osha1910-269.definition},
howpublished = {\url{https://www.groundingreference.com/data/gloss.step-voltage.osha1910-269.definition/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-10-29}