Data record gloss.ground-mat.osha1910-269.definition

Verified 2026-11-02 Confidence: High

Appendix C to 29 CFR 1910.269 (section III.A, definitions) describes a ground mat, also called a grounding grid, as a metallic mat or grating, installed temporarily or permanently, that establishes an equipotential surface and provides points for attaching grounds. The buried grid of a switchyard or substation is the permanent form; the appendix explains that an equipotential zone protects the workers within it and not those wholly or partly outside it.

Provenance29 CFR 1910.269 supports data record gloss.ground-mat.osha1910-269.definition, which is cited on the entry Ground mat.SOURCE29 CFR 1910.26929 CFR 1910.269Regulation, clause Appendix C, III.ADATA RECORDgloss.ground-mat.osha1910-269.definitiongloss.ground-mat.osha191..Verified 2026-11-02ENTRYGround matGround matNo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
Source29 CFR 1910.269Regulation, clause Appendix C, III.A
Data recordgloss.ground-mat.osha1910-269.definitionVerified 2026-11-02
EntryGround matNo revisions
Subject
Ground mat (Glossary)
Kind
Definition
Source
29 CFR 1910.269, current edition, clause Appendix C, III.A, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
Also stated in
  • Source passage: 29 CFR 1910.269, Appendix C, section III.A, definition of "ground mat (grounding grid)" (eCFR current as of 2026-10-26).
    Read the reference passage

    III. Protecting Workers From Hazardous Differences in Electrical Potential - A. Definitions

    "Ground mat (grounding grid). A temporarily or permanently installed metallic mat or grating that establishes an equipotential surface and provides connection points for attaching grounds."

    29 CFR 1910.269, Appendix C, section III.A, definition of "ground mat (grounding grid)", eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269

    The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.

  • Stated independently by FIST 5-1, section 8 Background, page 31 (July 2005).
    Read the reference passage

    8. Switchyard and Substation Protective Grounding

    "Both threephase and single-phase-to-ground faults should be considered when determining the maximum available fault current at a grounded worksite. Buried ground mat conductors should be present within the confines (perimeter fence) of the station. The ground mat provides a common and permanent grounding electrode for bonding all non-current carrying conductive parts of equipment in the station (circuit breaker and transformer tanks, metal structures, fencing, etc.). It also conducts ground fault current into the earth which returns to remote grounded current sources."

    FIST 5-1, section 8 Background, page 31, July 2005. Agency copy of FIST 5-1

    The current standard governs; this passage is a public-domain description of the practice dated July 2005.

  • Stated independently by FIST 5-1, section 8 Background, page 32 (July 2005).
    Read the reference passage

    8. Switchyard and Substation Protective Grounding

    "Within the perimeter fence of the station, the ground mat should control all step and touch potentials to safe levels during a ground fault. An exception to this rule may be in areas of the yard without equipment (empty bays) and lacking buried ground mat conductors. The ground mat also provides the ground electrode connection for protective grounds."

    FIST 5-1, section 8 Background, page 32, July 2005. Agency copy of FIST 5-1

    The current standard governs; this passage is a public-domain description of the practice dated July 2005.

Beside
gloss.step-voltage.osha1910-269.definition; gloss.touch-voltage.osha1910-269.definition

History

Every recorded change to this data record, oldest first.
DateChange
2026-11-02created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record gloss.ground-mat.osha1910-269.definition." Grounding Reference. 2026-11-02. https://www.groundingreference.com/data/gloss.ground-mat.osha1910-269.definition/.
Grounding Reference, Data record gloss.ground-mat.osha1910-269.definition (Nov. 2, 2026), https://www.groundingreference.com/data/gloss.ground-mat.osha1910-269.definition/.
@misc{etr-data-gloss-ground-mat-osha1910-269-definition,
  title = {Data record gloss.ground-mat.osha1910-269.definition},
  howpublished = {\url{https://www.groundingreference.com/data/gloss.ground-mat.osha1910-269.definition/}},
  organization = {Grounding Reference},
  publisher = {Grounding Reference},
  year = {2026},
  note = {last substantive change 2026-11-02}
}
{{cite web |title=Data record gloss.ground-mat.osha1910-269.definition |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/gloss.ground-mat.osha1910-269.definition/ |date=2026-11-02 |access-date=}}