Appendix C to 29 CFR 1910.269 (section II.B) describes touch potential as the voltage between an energized grounded object, the electrode, and the feet of a person in contact with the object while fault current flows; a voltage carried by a bonded structure, vehicle or ground lead to a point away from the electrode is called a transferred touch potential in the same sense. The industry term for the quantity is touch voltage.
| Step | Item | Detail |
|---|---|---|
| Source | 29 CFR 1910.269 | Regulation, clause Appendix C, II.B |
| Data record | gloss.touch-voltage.osha1910-269.definition | Verified 2026-10-29 |
| Entry | Touch voltage | No revisions |
- Subject
- Touch voltage (Glossary)
- Kind
- Definition
- Source
- 29 CFR 1910.269, current edition, clause Appendix C, II.B, 1910.269 - Electric power generation, transmission, and distribution (with Appendices A to G; Appendix B, Working on Exposed Energized Parts), OSHA. Regulation text. Agency copy of 29 CFR 1910.269
- Also stated in
- Source passage: 29 CFR 1910.269, Appendix C, section II.B (eCFR current as of 2026-10-26).
Read the reference passage
II. Voltage-Gradient Distribution - B. Step and touch potentials
"Touch potential is the voltage between the energized grounded object (again, the electrode) and the feet of a person in contact with the object."
29 CFR 1910.269, Appendix C, section II.B, eCFR current as of 2026-10-26. Agency copy of 29 CFR 1910.269
The current standard governs; this passage is a public-domain description of the practice dated eCFR current as of 2026-10-26.
- Stated independently by FIST 5-1, section 6.2.2, pages 20 to 21 (July 2005).
Read the reference passage
6.2.2 Cable Length
"The lineworker exposure voltage (line conductor to structure touch potential) for transmission lines grounded as shown in Section 9 will not exceed about three times the calculated ground cable resistance voltage drop. Therefore, the calculated ground cable resistance voltage drop should not exceed about 25 volts in order to meet the 75-volt safety criteria from paragraph 4.1."
FIST 5-1, section 6.2.2, pages 20 to 21, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 8.7, page 37 (July 2005).
Read the reference passage
8.7 Mobile Equipment
"In switchyards and substations having grounds mats, or at other locations where ground mats are used to control earth surface voltage potential, all mobile equipment and vehicles involved at a worksite within the station (ground mat area) shall be grounded (bonded) to the ground mat. Ground cables on reels or looped on the vehicle shall be completely unwound to allow thorough inspection of the cable prior to use and to minimize cable inductance."
FIST 5-1, section 8.7, page 37, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 8.7, page 37 (July 2005).
Read the reference passage
8.7 Mobile Equipment
"Cranes can create special touch potential hazards if used to make picks outside the station (beyond perimeter fence or ground mat area). Therefore, if possible, do not have the crane inside the station yard making picks outside the perimeter fence, off the mat."
FIST 5-1, section 8.7, page 37, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 8 Background, page 31 (July 2005).
Read the reference passage
8. Switchyard and Substation Protective Grounding
"Both threephase and single-phase-to-ground faults should be considered when determining the maximum available fault current at a grounded worksite. Buried ground mat conductors should be present within the confines (perimeter fence) of the station. The ground mat provides a common and permanent grounding electrode for bonding all non-current carrying conductive parts of equipment in the station (circuit breaker and transformer tanks, metal structures, fencing, etc.). It also conducts ground fault current into the earth which returns to remote grounded current sources."
FIST 5-1, section 8 Background, page 31, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 8 Background, page 32 (July 2005).
Read the reference passage
8. Switchyard and Substation Protective Grounding
"Within the perimeter fence of the station, the ground mat should control all step and touch potentials to safe levels during a ground fault. An exception to this rule may be in areas of the yard without equipment (empty bays) and lacking buried ground mat conductors. The ground mat also provides the ground electrode connection for protective grounds."
FIST 5-1, section 8 Background, page 32, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 9.1.5, pages 40 to 41 (July 2005).
Read the reference passage
9.1.5 Overhead Ground Wires
"The importance of bonding overhead ground wires to the worksite structure for electrical safety cannot be overemphasized. Otherwise, a lethal transferred touch voltage can appear between the structure steel and wire during an accidental energization of the grounded line, or in some cases due to coupling from a nearby energized line."
FIST 5-1, section 9.1.5, pages 40 to 41, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 9.5.2, page 44 (July 2005).
Read the reference passage
9.5.2 Contact With Grounded Vehicles at Worksite
"Vehicles and equipment that are bonded to the worksite grounding system can present a hazardous transferred touch voltage with the surrounding ground (earth) surface. Therefore, any vehicle or equipment bonded to the worksite grounding system (including conductive winch lines) and requiring sustained contact while standing on the ground, shall be equipped with an insulated platform or conductive mat bonded to the vehicle or equipment for the operator to stand on (figure 22)."
FIST 5-1, section 9.5.2, page 44, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, section 9.5, page 44 (July 2005).
Read the reference passage
9.5 Surface Equipment and Vehicle Grounding
"The purpose of bonding equipment and vehicles to the worksite grounding system (during de-energized work) is to control and minimize transferred touch potentials between the structure, equipment, and vehicle during an accidental energization of the line. Vehicle and equipment grounds are to be used in conjunction with properly installed personal protective grounds. Ground cables used for equipment and vehicle grounding shall be no smaller than #1/0 copper and shall be tested in accordance with Section 10. In no instance shall vehicle and equipment grounds be used in place of personal protective grounds."
FIST 5-1, section 9.5, page 44, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by FIST 5-1, Appendix F2 D, page 73 (July 2005).
Read the reference passage
D. Example and Discussion of a Structure Touch Voltage
"Probably the most common example of a related touch voltage is the worker operating a disconnect switch with the remote possibility of the switch faulting to the structure."
FIST 5-1, Appendix F2 D, page 73, July 2005. Agency copy of FIST 5-1
The current standard governs; this passage is a public-domain description of the practice dated July 2005.
- Stated independently by UFM 3-560-01, section 7-3, page 79, the first three sentences (13 March 2026).
Read the reference passage
7-3 AERIAL LIFT TRUCK VEHICLE GROUNDING
"Ground and bond each vehicle being used at the job site when any parts of it will come within the minimum approach distances of Table 3-1. When in transit or when parked with no load and all booms lowered, the vehicle may be ungrounded if it is located outside the restricted approach boundary. Ensure the workers and the vehicle operator are aware of step and touch potential hazards near vehicles as well as near permanent and temporary ground rods and electrodes."
UFM 3-560-01, section 7-3, page 79, the first three sentences, 13 March 2026. Agency copy of UFM 3-560-01
The current standard governs; this passage is a public-domain description of the practice dated 13 March 2026.
- Stated independently by UFM 3-560-01, section 9-2.1, page 104, the first bullet of the run-in paragraph Airbreak Switches, quoted from its first word; the line-end hyphen of "iron-mesh" is kept as the page prints it (13 March 2026).
Read the reference passage
9-2.1 Air Switches. Airbreak Switches
"Provide ground mats for the operator to stand on for all substation airbreak switches when operating. Either fixed or portable small iron-mesh mats must be used. The mats must be electrically connected to the operating rod and the substation ground grid to equalize the ground gradient and prevent any potential differences in case of insulation failure or flashover."
UFM 3-560-01, section 9-2.1, page 104, the first bullet of the run-in paragraph Airbreak Switches, quoted from its first word; the line-end hyphen of "iron-mesh" is kept as the page prints it, 13 March 2026. Agency copy of UFM 3-560-01
The current standard governs; this passage is a public-domain description of the practice dated 13 March 2026.
- Source passage: 29 CFR 1910.269, Appendix C, section II.B (eCFR current as of 2026-10-26).
History
| Date | Change |
|---|---|
| 2026-10-29 | created |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record gloss.touch-voltage.osha1910-269.definition." Grounding Reference. 2026-10-29. https://www.groundingreference.com/data/gloss.touch-voltage.osha1910-269.definition/.
Grounding Reference, Data record gloss.touch-voltage.osha1910-269.definition (Oct. 29, 2026), https://www.groundingreference.com/data/gloss.touch-voltage.osha1910-269.definition/.
@misc{etr-data-gloss-touch-voltage-osha1910-269-definition,
title = {Data record gloss.touch-voltage.osha1910-269.definition},
howpublished = {\url{https://www.groundingreference.com/data/gloss.touch-voltage.osha1910-269.definition/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-10-29}
}{{cite web |title=Data record gloss.touch-voltage.osha1910-269.definition |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/gloss.touch-voltage.osha1910-269.definition/ |date=2026-10-29 |access-date=}}