Clauses 6.4 and 6.5 of ANSI/TIA-607-E (2024) require bonding connectors listed for their application with a limited electrochemical potential difference against the busbar, green or green-marked insulation on insulated bonding conductors, and labels telling anyone who finds a conductor loose, or needs to remove it, to call the building telecommunications manager.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.structure.connectors-and-identification, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 6.4, 6.5DATA RECORDstd.tia-607-e.structure.connectors-and-identificationstd.tia-607-e.structure...Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/TIA-607-ELicensed standard, clause 6.4, 6.5
Data recordstd.tia-607-e.structure.connectors-and-identificationVerified 2026-10-25
EntryANSI/TIA-607-ENo revisions
Subject
ANSI/TIA-607-E (Standards)
Kind
Standard scope
Source
ANSI/TIA-607-E, 2024 edition, clause 6.4, 6.5, page 34, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-25created
2026-10-25revised
2026-10-25review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.tia-607-e.structure.connectors-and-identification." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.structure.connectors-and-identification/.