Data record std.tia-607-e.method.two-point-paths

Verified 2026-10-25 Confidence: High

Clause 9.1 of ANSI/TIA-607-E (2024) recommends two-point measurements from each primary or secondary busbar to the electrical ground in the distributor and to structural metal, from the primary to each secondary busbar, and from structural metal to electrical ground, taken before any telecommunications equipment goes in, since parallel paths through equipment can invalidate the result.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.method.two-point-paths, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 9.1DATA RECORDstd.tia-607-e.method.two-point-pathsstd.tia-607-e.method.two..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/TIA-607-ELicensed standard, clause 9.1
Data recordstd.tia-607-e.method.two-point-pathsVerified 2026-10-25
EntryANSI/TIA-607-ENo revisions
Subject
ANSI/TIA-607-E (Standards)
Kind
Method fact
Source
ANSI/TIA-607-E, 2024 edition, clause 9.1, page 53, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-25created
2026-10-25revised
2026-10-25review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.tia-607-e.method.two-point-paths." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.method.two-point-paths/.