Clause 9.2.2 of ANSI/TIA-607-E (2024) describes the clamp-on meter as measuring an electrode in a multi-grounded system without disconnecting it, and advises against it for commissioning new grounds, for soil resistivity, for complex grounds with metallic loops and wherever a client requires a method incorporated in a reference standard.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.method.clamp-on, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 9.2.2DATA RECORDstd.tia-607-e.method.clamp-onstd.tia-607-e.method.cla..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/TIA-607-ELicensed standard, clause 9.2.2
Data recordstd.tia-607-e.method.clamp-onVerified 2026-10-25
EntryANSI/TIA-607-ENo revisions
Subject
ANSI/TIA-607-E (Standards)
Kind
Method fact
Source
ANSI/TIA-607-E, 2024 edition, clause 9.2.2, page 55, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.