Data record std.tia-607-e.external.design-not-acceptance

Verified 2026-10-25 Confidence: Medium

In ANSI/TIA-607-E (2024) the electrode system resistance appears as a design requirement in clause 8.1 rather than as a measured acceptance limit; clause 9.2 describes how to measure it but no clause requires the measured value to meet the design figure.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.external.design-not-acceptance, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 8.1, 9.2DATA RECORDstd.tia-607-e.external.design-not-acceptancestd.tia-607-e.external.d..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/TIA-607-ELicensed standard, clause 8.1, 9.2
Data recordstd.tia-607-e.external.design-not-acceptanceVerified 2026-10-25
EntryANSI/TIA-607-ENo revisions
Subject
ANSI/TIA-607-E (Standards)
Kind
Standard scope
Source
ANSI/TIA-607-E, 2024 edition, clause 8.1, 9.2, page 51, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-25created
2026-10-25revised
2026-10-25review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.tia-607-e.external.design-not-acceptance." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.external.design-not-acceptance/.