Clause 7.5.4 of ANSI/TIA-607-E (2024) requires each bonding backbone to run continuously from the primary busbar to the farthest secondary busbar along the backbone pathways, protected from damage and with as few splices as possible, and excludes cable shields, conduit and water piping from serving as a backbone.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.design.tbb-design, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 7.5.4DATA RECORDstd.tia-607-e.design.tbb-designstd.tia-607-e.design.tbb..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions