Clause 7.5.4 of ANSI/TIA-607-E (2024) requires each bonding backbone to run continuously from the primary busbar to the farthest secondary busbar along the backbone pathways, protected from damage and with as few splices as possible, and excludes cable shields, conduit and water piping from serving as a backbone.
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/TIA-607-E | Licensed standard, clause 7.5.4 |
| Data record | std.tia-607-e.design.tbb-design | Verified 2026-10-25 |
| Entry | ANSI/TIA-607-E | No revisions |
- Subject
- ANSI/TIA-607-E (Standards)
- Kind
- Standard scope
- Source
- ANSI/TIA-607-E, 2024 edition, clause 7.5.4, page 42, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.
History
| Date | Change |
|---|---|
| 2026-10-25 | created |
| 2026-10-25 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.tia-607-e.design.tbb-design." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.design.tbb-design/.
Grounding Reference, Data record std.tia-607-e.design.tbb-design (Oct. 25, 2026), https://www.groundingreference.com/data/std.tia-607-e.design.tbb-design/.
@misc{etr-data-std-tia-607-e-design-tbb-design,
title = {Data record std.tia-607-e.design.tbb-design},
howpublished = {\url{https://www.groundingreference.com/data/std.tia-607-e.design.tbb-design/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-10-25}
}{{cite web |title=Data record std.tia-607-e.design.tbb-design |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/std.tia-607-e.design.tbb-design/ |date=2026-10-25 |access-date=}}