Data record std.tia-607-e.design.pbb-installation

Verified 2026-10-25 Confidence: Medium

Clause 7.2.1 of ANSI/TIA-607-E (2024) requires the primary bonding busbar to be placed as close as practical to the electrical panelboard while keeping code clearances, mounted on a listed insulator that isolates it from its support and cleaned before connectors are fitted, and clause 7.2.3 limits its main connections to exothermic welds and listed two-hole lugs.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.design.pbb-installation, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 7.2.1, 7.2.3DATA RECORDstd.tia-607-e.design.pbb-installationstd.tia-607-e.design.pbb..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/TIA-607-ELicensed standard, clause 7.2.1, 7.2.3
Data recordstd.tia-607-e.design.pbb-installationVerified 2026-10-25
EntryANSI/TIA-607-ENo revisions
Subject
ANSI/TIA-607-E (Standards)
Kind
Standard scope
Source
ANSI/TIA-607-E, 2024 edition, clause 7.2.1, 7.2.3, page 38, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-25created
2026-10-25revised
2026-10-25review_status unreviewed -> software_reviewed

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record std.tia-607-e.design.pbb-installation." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.design.pbb-installation/.