Data record std.tia-607-e.design.bolted-racks
Verified 2026-10-25 Confidence: High
Clause 7.7 of ANSI/TIA-607-E (2024) does not accept ordinary frame bolts as proof of continuity in a bolted rack or cabinet, so it calls for tested bonding hardware or paint removal at bonding contact points, and requires doors and removable panels to be bonded by jumper or through the frame.
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/TIA-607-E | Licensed standard, clause 7.7 |
| Data record | std.tia-607-e.design.bolted-racks | Verified 2026-10-25 |
| Entry | ANSI/TIA-607-E | No revisions |
- Subject
- ANSI/TIA-607-E (Standards)
- Kind
- Standard scope
- Source
- ANSI/TIA-607-E, 2024 edition, clause 7.7, page 45, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.
History
| Date | Change |
|---|---|
| 2026-10-25 | created |
| 2026-10-25 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.tia-607-e.design.bolted-racks." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.design.bolted-racks/.
Grounding Reference, Data record std.tia-607-e.design.bolted-racks (Oct. 25, 2026), https://www.groundingreference.com/data/std.tia-607-e.design.bolted-racks/.
@misc{etr-data-std-tia-607-e-design-bolted-racks,
title = {Data record std.tia-607-e.design.bolted-racks},
howpublished = {\url{https://www.groundingreference.com/data/std.tia-607-e.design.bolted-racks/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-10-25}
}{{cite web |title=Data record std.tia-607-e.design.bolted-racks |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/std.tia-607-e.design.bolted-racks/ |date=2026-10-25 |access-date=}}