Clause 7.7 of ANSI/TIA-607-E (2024) does not accept ordinary frame bolts as proof of continuity in a bolted rack or cabinet, so it calls for tested bonding hardware or paint removal at bonding contact points, and requires doors and removable panels to be bonded by jumper or through the frame.

ProvenanceANSI/TIA-607-E supports data record std.tia-607-e.design.bolted-racks, which is cited on the entry ANSI/TIA-607-E.SOURCEANSI/TIA-607-EANSI/TIA-607-ELicensed standard, clause 7.7DATA RECORDstd.tia-607-e.design.bolted-racksstd.tia-607-e.design.bol..Verified 2026-10-25ENTRYANSI/TIA-607-EANSI/TIA-607-ENo revisions