Data record std.tia-607-e.design.rooms
Verified 2026-10-25 Confidence: Medium
Clauses 7.1.2 and 7.1.3 of ANSI/TIA-607-E (2024) require a primary or secondary bonding busbar in every equipment room and telecommunications room, and a secondary busbar in every computer room (or a primary one where the design calls for it), with any supplementary bonding network in that room bonded to the busbar.
| Step | Item | Detail |
|---|---|---|
| Source | ANSI/TIA-607-E | Licensed standard, clause 7.1.2, 7.1.3 |
| Data record | std.tia-607-e.design.rooms | Verified 2026-10-25 |
| Entry | ANSI/TIA-607-E | No revisions |
- Subject
- ANSI/TIA-607-E (Standards)
- Kind
- Standard scope
- Source
- ANSI/TIA-607-E, 2024 edition, clause 7.1.2, 7.1.3, page 35, Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises, TIA.
History
| Date | Change |
|---|---|
| 2026-10-25 | created |
| 2026-10-25 | revised |
| 2026-10-25 | review_status unreviewed -> software_reviewed |
Cite this page
Cite the governing standard for the fact itself; cite this page as the finding aid.
"Data record std.tia-607-e.design.rooms." Grounding Reference. 2026-10-25. https://www.groundingreference.com/data/std.tia-607-e.design.rooms/.
Grounding Reference, Data record std.tia-607-e.design.rooms (Oct. 25, 2026), https://www.groundingreference.com/data/std.tia-607-e.design.rooms/.
@misc{etr-data-std-tia-607-e-design-rooms,
title = {Data record std.tia-607-e.design.rooms},
howpublished = {\url{https://www.groundingreference.com/data/std.tia-607-e.design.rooms/}},
organization = {Grounding Reference},
publisher = {Grounding Reference},
year = {2026},
note = {last substantive change 2026-10-25}
}{{cite web |title=Data record std.tia-607-e.design.rooms |website=Grounding Reference |publisher=Grounding Reference |url=https://www.groundingreference.com/data/std.tia-607-e.design.rooms/ |date=2026-10-25 |access-date=}}